Assembly of wires
NOTICE

Loose and slack cable connections!
Malfunctions due to loose contacts.
- Observe metal sleeve length and stripping length according to table.
- Use a suitable pressing tool.
- Make sure that all wires are inserted into the wire-end sleeve.
- After inserting the cable into the terminal, check that it is firmly seated.
Cross section | Wire end ferrule | Metal sleeve length | Stripping length |
|---|---|---|---|
0.5…1 mm² | With plastic collars | 10 mm | 12 mm |
0.5…1,5 mm² | Without plastic collars | 10 mm | 10 mm |
0.2…1.5 mm² | Without wire end ferrule | - | 10 mm |