Assembly of wires

NOTICE

notice

Loose and slack cable connections!

Malfunctions due to loose contacts.

  1. Observe metal sleeve length and stripping length according to table.
  2. Use a suitable pressing tool.
  3. Make sure that all wires are inserted into the wire-end sleeve.
  4. After inserting the cable into the terminal, check that it is firmly seated.
Wire end ferrules and stripping length

Cross section

Wire end ferrule

Metal sleeve length

Stripping length

0.5…1 mm²
(20…17 AWG)

With plastic collars

10 mm

12 mm

0.5…1,5 mm²
(20…16 AWG)

Without plastic collars

10 mm

10 mm

0.2…1.5 mm²
(24…16 AWG)
Solid or fine strand

Without wire end ferrule

-

10 mm