Electrical installation
DANGER

Electrical voltage in the vicinity of the device!
Danger to life due to electric shock !
- This device is intended for installation in control cabinets or machines that can be operated under dangerous voltages. For any work on the device
- Switch off the supply voltage of the control cabinet or machine.
- Secure it against switching on.
- Wait until all drives has been stopped in order that no regenerative energy can be generated.
- Never bridge upstream protective devices. Also not for test purposes.
- Lay the control and power cables separately (approx. 10–20 cm (4"-8") distance).
- Lay junctions with power cables at right angles.
- Electromagnetic interference can be prevented by taking the following measures:
- Always apply the shielding over as large an area as possible.
- Position the shield as close as possible to the terminal.
- Always use twisted-pair, shielded cables for analogue control lines. Connect the shield to the source on one side.
- Twist digital control cables. Shielding may be required for distances of 3 metres or more. In this case, hang up on both sides.
- The 24 V supply must not fall below or exceed the input voltage range specified in the technical data, regardless of the operating condition.
- The wiring, as well as the short-circuit and overcurrent protection, must be carried out in accordance with the applicable standards and regulations, taking into account the product’s electrical specifications.
- If power cuts are to be bridged, an external UPS must be used.