Montage
The product is fitted directly onto a DIN rail inside an industrial control cabinet. The DIN rail allows the product to be fitted inside a control cabinet with the heat sink (as viewed from the front) on the left-hand side. This promotes vertical airflow within a control cabinet and ensures maximum heat dissipation.
- The permitted types of top-hat rail are TH35/7.5 and TH35/15 in accordance with EN 60715.
- To prevent problems with vibration, the top-hat rail should be connected to the mounting bracket at intervals of no more than 200 mm.
- Ensure that heat does not build up in multi-storey structures.