Power supply: 24 V DC (X6)

The 3-pole terminal X6 is connected to an external 24 V DC supply via the matching plug supplied. Only connect the appliance to a mains power supply that falls within the specified voltage range, complies with the product’s electrical specifications as set out in this user manual and on the product’s rating plate, and provides the necessary safety and protection features.

WARNING

warning

Power supply during operation and in the event of a fault

Risk of electric shock or fire.

  1. Power supply in accordance with DIN EN IEC 62368-1; use LPS and PS2.
  2. Use the voltage specified on the type plate in accordance with PELV.
  3. is capable of supplying the required power as stated on the type plate.
  4. In the event of a short circuit, it can only supply a limited amount of current.
  5. Cannot supply more than 100 kVA of continuous power under any load condition.

 

The on/off switch (S1) does not disconnect the unit from the power supply. Ensure that a suitable isolating device (fuse/circuit breaker) is fitted, which is rated for the cross-sectional area of the supply cable.

 

Terminal block X6 voltage suypply

X6.1

DC +24V

X6.2

GND

X6.3

GND

➀

Fixing screw

➀

Fixing screw

➁

Locking lever for releasing the cables

 

NOTICE

notice

Loose and slack cable connections!

Malfunctions due to loose contacts.

  1. Observe metal sleeve length and stripping length according to table.
  2. Use a suitable pressing tool.
  3. Make sure that all wires are inserted into the wire-end sleeve.
  4. After inserting the cable into the terminal, check that it is firmly seated.

 

Wire ferrules and strip length

Cross-section

wire end ferrule

Metal sleeve length

Stripping length

0.25–0.75 mm²
(23–19 AWG)

With a plastic collar

10 mm

10 mm

0.5…1.5 mm²
(20…16 AWG)

Without a plastic collar

10 mm

10 mm

 

NOTICE

notice

Malfunction and fire hazard due to incorrect wiring

Cabling is not included in the scope of delivery and must be provided by the user.

  1. To protect the product and any connected peripherals, ensure that the power cables are of the correct diameter to withstand the maximum available current.
  2. Clearly label the supply lines (+/-) to ensure safe connection to the external 24 V DC power supply.
  3. Use only copper conductors for a minimum temperature of 105 °C.

 

 

NOTICE! To disconnect a cable, press down on the relevant orange locking lever using a suitable tool.