Terminal block X6
Voltage supply occcurs via terminal block X6. Depending on the variant, a 4-, 8-, 12- or 16-pole pluggable terminal block is used.
X6 | PIN | Designation | Notes |
|---|---|---|---|
| 1 | 24V | DC 24 V supply voltage (internally connected to pin 2) |
2 | 24V | DC 24 V supply voltage (internally connected to pin 1) | |
3 | 0V | Reference potential to 24 V (internally connected to pin 4) | |
4 | 0V | Reference potential zu 24 V (internally connected to pin 3) | |
5-8 | - | ||
9-12 | - | ||
13-16 | - |
The terminals for the voltage supply are always identical, independent of the above design.
Notes
The connection terminals X6.1/X6.2 and X6.3/X6.4 are connected internally to create a daisy chain if required.
The 0 V terminals are not internally connected to earth.
The maximum permissible current via the terminal is 9.5 A and must not be exceeded.
The cables must be designed according to the current.