CAN

The CAN bus is connected via terminal block X6. Depending on the variant, an 8, 12 or 16-pole plug-in terminal block is used.

Assignment of terminal block X6

X6

PIN

Designation

Notes

1-4

-

Voltage supply

5

Shielding

Shield connection (FE)

6

CAN_GND

Reference potential CAN
(galvanically isolated)

7

CAN_H

CAN data signal high

8

CAN_L

CAN data signal Low

9-12

-

RS485

13-16

-

RS232

The terminals for the CAN bus are always identical, independent of the above design.

 

Specification

Fieldbus type

CAN

Transmission level

In accordance with DIN ISO 11898; ISO High Speed

Transmission speed

20, 25, 50, 100, 125, 250, 500, 800, 1000 kbit/s; adjustable via CN01

Transmission medium

Twisted pair
maximum cable length 40 m

Potential separation

Functional isolation between CAN terminals and control potential.

Bus termination

120 Ω external between (CAN High and CAN Low) at both ends of the bus cable.

Connection

Connection CAN bus

 

Terminal X6

Designation

Note

5

Shielding

Total shield

6

CAN GND

CAN ground (can be wired depending on the customer participant)

7

CAN High

Data cable CAN_H and CAN_L twisted;

no internal bus termination

8

CAN Low